FK1230 (FK-5-1-12)

Enquire Now

Typical FK1230 (FK-5-1-12) Clean Agent System Layout

The fire extinguishing system uses FK1230 as fire suppression agent, which is an next-generation alternative for Halon replacement. FK1230 is used to protect an area that contains valuable equipmentor materials, including but not limited to Museums, Banks, Clean Rooms, Data Centers, and Libraries.FK1230 leaves no residue behind, has zero ozone depletion and has the lowest atmospheric lifetime among halocarbon alternatives. FK1230 extinguishes the fire by heat absorption, which results in lessdowntime, less cleanup, limited business interruption, and is environment friendly.

What is FK1230 (FK-5-1-12) ?

FK1230 (FK-5-1-12) is a second generation fire suppressant listed in NFPA 2001 and EPA’s Significant New Alternatives Program (SNAP).

How Does it Work ?

FK1230 is a synthetic / chemical fire suppression gas and extinguishes fire by removing the fire’s heat elements. It doesnot work by oxygen starvation. The concentration of FK-5-1-12 is typically between 4.5 % to 5.9 % of the room volume.

Founded in 2015 at Mangaon Midc, Maharashtra, We Specialize in Manufacturing and Supplying Ul-Listed Clean Agent Fire Suppression Systems Designed for Maximum Safety and Efficiency. Our State-Of-The-Art Infrastructure Includes Dedicated Departments for Quality Testing, Warehousing, Procurement, Sales, and Marketing, Ensuring Seamless Operations. with a Leadership Team of Highly Qualified Technocrats Boasting a Collective Experience of 100 Years, We Are Committed to Delivering High-Performance Fire Suppression Solutions.

Fire Suppression Time:

The clean agent fire suppression system achieves discharge in 10 seconds. The fire will be extinguished within 30 seconds.

Safe for Humans and the Environment

FK1230 Clean Agent fire suppression system that offers a widemargin of safety. It has non ozone depleting potential, and has anatmospheric lifetime of only 5 days. Person present during thedischarge of FK-5-1-12, are not adversely affected by it.

Why 42 Bar System ?

While a 25 bar system is suitable for the majority of hazards. A 42 bar offers additional flexibility in the design of systems to protect larger or more complex hazards. These include those incorporating directional valves for multi-zone protection and where system cylinders are to be located further from the protected area.

FK1230 (FK-5-1-12) Fire Suppression Agent

FK1230 (FK-5-1-12) agent compiles with NFPA Standard 2001 standard on “Clean Agent Fire Extinguishing Systems.” EPA SNAP Program (Significant New Alternate Policy) The FK1230 is classified as suitable for use in occupied areas and has no ozone depleting potential (ODP).

Description:

FK1230 systems reach extinguishing levels in 40 seconds or less, stopping ordinary combustible, electrical, and flam ’ mable liquid fires before they can cause significant damage. That s the fastest fire protection available, When a fire is extinguished this quickly, it means less damage, lower repair costs, and an extra margin of safety for people. It also means less downtime and disruption of business.

Physical & Chemical Properties

Empirical formulaeCF3CF2C(O)CF(CF3)2
IUPAC DesignationDodecafluoro-2-methylpentan-3one
ASHRAE DesignationFK-5-1-12
Molecular Weight316.04
Boiling Point at 1 Atm49.2 °C (120.6 °F )
Freezing Point-108.0⁰C ( -162.4°F )
No Observed Adverse Effect Level10 %
Lowest Observed Adverse>10%

NFPA 2001, Requirements for Minimum Values

AgentClass A MECClass A DesignClass C DesignClass B Design
FK-5-1-123.54.54.55.9

Environmentally Friendly:

DescriptionFK-5-1-12 (FK1230)
Ozone Depletion Potential (ODP)0
Global Warming Potential (GWP)1
Atmospheric Lifetime (Days)5
SNAP (Yes / No)Yes